FACP IQ8Control M

BROŞÜR İÇİN TIKLAYIN


  • Max. five micromodules, with peripheral module Part No. 772477, up to five esserbus loop modules (system supports up to 635 digital loop addresses in total)
  • Max. seven micromodules, with extension module Part No. 772476, up to seven esserbus loop modules (system supports up to 889 digital loop addresses in total)
  • Short circuit and open circuit tolerant loop operation
  • Loop installation with I-Y(ST)Y 0.8 mm cable for a maximum length of 3.5 km
  • Up to 127 esserbus devices (fire detectors and/or manual call points)/detector zones per loop
  • Up to 32 esserbus transponders per loop/operation of wireless components (see chapter 10)
  • Operation types TM and PM as per DIN VDE 0833 - 2 to avoid unwanted alarms being triggered
  • Fire brigade operating panel and transmission interface on the peripheral module
  • Three common relays, freely programmable, monitored, floating for up to 30 V DC/1A (on the peripheral module)
  • TTY or RS 485 or RS 232 interface
  • Integration in the short circuit and open circuit resistant essernet network with up to 31 fire detection panels depends on transmission rate
  • Connection to graphical supervisor WINMAG via serial essernet interface (SEI)
  • Operating panel with alphanumerical display
  • Large display with 8 rows with 40 characters. As follows rated - four rows with 40 characters for the status information (first and last message), and the other four rows with 40 characters are used for system information e.g. “Sounders Off”
  • Event memory for up to 10,000 events
  • All Systems 8000 micromodules are compatible
  • Printer interface for internal printer
  • Two batteries with monitoring circuit
  • Monitored input for external power supply unit

Additional features for powered loop

  • Max. 6 powered loops and expandable up to 127 loop devices (per loop) in mixed mode / loop powered and non-loop powered (system supports up to 762 digital loop addresses in total)
  • esserbus-PLus (Powered Loop) supplied, synchronously controlled, acoustic alarm signaling devices as per DIN EN 54 - 3 with alarm tone as per DIN 33404
  • Up to 48 powered loop base sounders (Series 9200) per loop
  • Up to 32 powered loop IQ8Alarm / IQ8Alarm Plus devices per loop
  • Up to 64 powered loop IQ8Alarm Plus So / FSo devices per loop
  • Up to 48 IQ8Quad with alarm device per loop